Home / Xitron / Xitron Power Analyzer / Xitron 2802 Power Quality Analyzer Datalogger Harmful Harmonic Component Analyzer-Dual Channel
On sale!

Xitron 2802 Power Quality Analyzer Datalogger Harmful Harmonic Component Analyzer-Dual Channel

$4,495.00 $4,248.00

Xitron 2802 Advanced  2-Channel  Harmonic Power Quality Analyzer

The Xitron 2802 measures and displays volts, current, power, frequency, harmonics (to the 100th), THD, PF, CF, K-Factor, Triplens, inrush, distortion, glitches, and much more. Internal Shunts and External Shunts available.

SKU: Xitron-2801-2 Categories: Xitron, Xitron Power Analyzer Tags: CF, distortion, glitch capture, inrush current, K-Factor, PF, Power Harmonic Analyzer, THD, Triplens, Xitron 2-Channel Power Analyzer
  • Description
  • Product Inquiry
  • Reviews (0)

Product Description

Xitron 2802 Power Quality Analyzer Datalogger Harmonic Analyzer

Dual & Single Channel Xitron 2802 Power Quality Analyzer Datalogger Harmonic Analyzer

Xitron 2802 Power Quality Analyzer Datalogger Harmonic Analyzer

Single-Dual Channel Power Analyzer

 The Xitron 2802 Power Quality Analyzer Datalogger Harmonic Analyzer is an ideal analyzer for standby power or Energy Star testing. It offers an extended measurement range from micro-amps to hundreds of amps and milli-volts to kilovolts Numeric results and waveforms can be displayed, read via the communication ports (RS-232, GPIB, USB, and Ethernet), or sent directly at full resolution to a USB printer.

Xitron 2802 Power Quality Analyzer Datalogger Harmonic Analyzer dissects waveforms with true 512-point precision. Peak, rms, rectified, and DC measurements of voltage, current and power are provided including continuous, inrush, startup and history modes, plus an integration mode for W-Hr, A-Hr, VA-Hr, as well as integrated average power.

Xitron 2802 Power Quality Analyzer Datalogger Harmonic Analyzer Features

  • Highest Performance-to-Cost ratio in the industry
  • Base accuracy <0.08%. Current and voltage accuracies specified to less than 1mArms and 1Vrms respectively (<0.2%)
  • Waveform Peak and Glitch capture
  • 2000Vpk and 150Apk measurable internally (external CT capable)
  • Integrated line switch and inrush waveforms
  • Graphics display shows numerical results, waveforms, bar graphs, startup & history charts with zoom & scroll features
  • Wiring loss and voltage burden compensation
  • DC charge and discharge measurements
  • Frequency Range: DC and 20mHz – 200kHz
  • Communications ports include USB, GPIB, and RS-232 standard

The Need to Measure Harmful  Crippling Harmonics is Solved with the Xitron 2802 Power Quality Analyzer Datalogger Harmonic Analyzer

Triplen Harmonics – The triplen harmonics are defined as the odd multiples of the 3rd harmonic (ex. 3rd, 9th, 15th, 21st etc.). Additionally, triplen harmonics are of particular concern because they are zero sequence harmonics, unlike the fundamental, which is positive sequence. Consequently, the fact is that the magnitude of these currents on the 3 phases are additive in the neutral. This can lead to very large currents circulating in the neutral, and unless the neutral is sufficiently oversized this can present a fire hazard. These currents can also circulate in the transformer causing significant overheating there as well. Single-phase power supplies for equipment such as electronic ballasts and PCs are the most significant source of Triplen harmonics.

Harmful 5th and 11th Harmful Harmonic

The 5th and 11th harmonics are also of particular concern to industry today.  Consequently, although the 5th harmonic is much more prevalent, both have a negative sequence.  This means that when distorted voltage containing the 5th or 11th harmonic is applied to a 3-phase motor, it will attempt to drive the motor in reverse, creating a negative torque.  In order to compensate for this negative torque, the motor must draw additional fundamental current.  Furthermore, this in turn can cause overheating and/or the tripping of over-current protection devices. Additionally, 6-Pulse adjustable speed drives are a major source of the 5th, 7th and 11th harmonics.  12-Pulse drives are significantly more expensive, and are a source of the 11th and 13th harmonics, but through their design are able to eliminate the 5th and 7th. The Xitron 2802 Power Quality Analyzer Datalogger Harmonic Analyzer is a great tool to use for this analysis.

 

Data Sheet Xitron_datasheet_2801-2802 e-QUOTE sales@ATEquip.com

Electrical Power Harmonics Explained

XiTRON Model Description Power Analyzers & Accessories MSRP Sales Price e-QUOTE for
Discount
Xitron 2000IN 2000IN DC Voltage and Current Calibrator $2,750

$2612.00 e-QUOTE 2000IN
Xitron 2000MN 2000MN DC Voltage, Current, & Temperature Calibrator $3,350 $3182.00 e-QUOTE 2000MN
Xitron 2553-950V-40A Xitron 2553E-950V-40A Three-Phase Power Analyzer $3,995.00 $3,755.00 e-QUOTE 2553E-950V-40A
Xitron 2801 Xitron 2801 single channel Power Analyzer $2,750.00 $2,312.00 e-QUOTE Xitron 2801
Xitron 2802 Xitron 2802 Dual (2) channel Power Analyzer $4,250.00 $3,995.00.00 e-QUOTE Xitron 2802
Xitron 2503AH-1CH Xitron 2503AH-1CH
Single Phase Power Analyzer
$6,495.00 $6105.00 e-QUOTE XiTRON 2503-1CH
Xitron 2503AH-2CH Xitron 2503AH-2CH
Dual Phase Power Analyzer Power Analyzer
$9,195.00 $8,643.00 e-QUOTE XiTRON 2503-2CH
Xitron 2503AH-3CH Xitron 2503AH-3CH
Three Phase Power Analyzer
$11,995.00 $11,275.00 e-QUOTE XiTRON 2503-3CH
Xitron XT3561 Xitron XT3561 1Ø-2Ø-3Ø Portable Power Quality Analyzer $6495.00 $6169.00 e-QUOTE XiTRON XT3561
* Insert a message
* Insert your name
* Insert your email address

Reviews

There are no reviews yet

Would you like to submit yours?

Be the first to review “Xitron 2802 Power Quality Analyzer Datalogger Harmful Harmonic Component Analyzer-Dual Channel” Cancel reply

Your email address will not be published.

*

*

Cart

  • No products in the cart.

Contact

Phone: 858-756-8742

Email: sales@atequip.com

Fax: 858-759-0157


copyright 2013 - ATEquip.com

HOME // SUPPORT // TERMS AND CONDITIONS // ABOUT // CONTACT US
designed by Armand Gilbert