MEGGERMegger 235303 Electrical Tool and Appliance Tester
MEGGERMegger DLRO10X Low Resistance Ohmmeter |
Megger 235303 Electrical Tool and Appliance Tester
Model 235303
Electrical Tool and Appliance Tester
Features:
Complete UL and ANSI testing in less than one minute
Safeguards tools and appliances against shock hazard
Reduces downtime and protects against injury and liability
Maintains compliance with OSHA safety regulations
Supports ISO 9001 Documentation
Megger 235303 Appliance Tester DESCRIPTION 
The MEGGER Tool and Appliance Tester model 235303 combines, in one portable unit, the three most frequently specified electrical safety tests for tools and appliances. In conformance to the latest UL and ANSI test requirements, the instrument performs tests of ground continuity, leakage current and electrical insulation. It also checks the nameplate current rating of the device.
MEGGER 235303 APPLICATIONS
Poorly maintained electrical tools can become a safety hazard and cause injury to personnel. Testing electrical tools on a regular basis is not only safe practice against costly repairs, but may even reduce liability. Applications for this handy instrument include inplant OSHA safety surveys and production line, tool room and repair shop safety checks.
Megger 235303 Ground Continuity Test
To check the integrity of the ground circuit between tool and plug, the instrument applies a 25-ampere test current to the ground circuit. If the ground circuit resistance exceeds the 0.10 W failure threshold, a safety interlock prevents further testing. A bypass switch is provided to allow testing of two-wire and double-insulated devices.
MEGGER 235303 Insulation Breakdown (HiPot) Tester
This test measures current through intsulation at high voltage to detect weak spots in the insulation that may cause failure in the future. Test voltage up to 3,000 volts ac may be applied, with the leakage current trip level adjustable from 0.3 to 12 mA by a front-panel control knob. Visual and audible alarms alert the operator to insulation failure.
MEGGER 235303 Operational Check
The Megger Tool and Appliance Tester (235303) also provides an operational check to verify the nameplate current rating of the tool and to determine if maintenance is required. Measurements up to 15 amperes are indicated.
Megger 235303 FEATURES AND BENEFITS
Full conformance to latest UL and ANSI test requirements
Meter readings - not just "good/bad" indications
Test procedures color-coded in sequence on front panel for
ease of use
Ground check bypass switch that permits testing of two-wire or double-insulated devices
Removable lid with metal tray to hold device under test
Heavy-duty case with carrying strap
Front-panel NEMA 5-15 output receptacle, with adapters available
to convert to 2-ampere plug or twist lock up to 30 amperes
Supports ISO 9001 Documentation
SPECIFICATIONS
Input Power Source 120 VAC ±10%, 60Hz, 15 A
Ground Check
Failure Threshold: 0.10 W
Maximum Test Voltage: 3 V, 60 Hz
Maximum Test Current: 25 A
Leakage Test
Indicates from 0 to 10 mA AC on a 3.5 inch analog scale
with 0.01 mA sensitivity
Test VOltage: 120 VAC, 60 Hz
Insulation Breakdown Test
Test Voltage: 0 to 3000 VAC, adjustable. Applied voltage indicated
on a 3.5 inch analog scale
Maximum Short-Circuit Current: 12.6 mA
Leakage Current Trip: Adjustable from 0.3 to 12 mA
Failure Indication: Audible and visual alarms
Operational Test
Indicates from 0 to 15 AAC on a 3.5 inch analog meter
Environmental
Operating Temperature: 50 to 104° F (10 to 40° C)
Storage Temperature: -22 to +131° F (-30 to +55° C)
Humidity: 5 to 95% RH
Dimensions: 10H x 13.5W x 10D inches (254H x 343W x 254D mm)
Weight: 28 lb (12.7 kg)
Megger 235303 ORDERING INFORMATION AT BOTTOM OF PAGE
|