Megger High Voltage Phase Comparitor 510900

Megger DETEX Voltage Detector 514500

Megger DETEX Voltage Detector 514242
Megger Pneumatic Glove Tester 512117

Megger Piezo Test Voltage Generator 510005

Megger DETEX Voltage Phase Detector
Megger Voltage Phase Comparitor 510900

Biddle Piezo High Voltage Generator 510006 |
Megger DETEX® Voltage Detectors and Phasing Testers
Non-Contact Phase Comparitor
Biddle Pole Phase Comparator (510900) The new single-pole phase comparator performs phase comparison with a single pole. There is no connecting cable to limit distance and mobility. The instrument memorizes reference phase, then visual and audible indicators signal whether additional phases are in phase or in opposition. This unit is not a voltage detector.
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
DETEX Voltage Detectors Non-Contact High Voltages
Tests Grounded AC Systems
For use on any grounded electrical system, DETEX Voltage Detectors are available in seven models that cover a range from distribution class to transmission line voltages up to 550 KV. Biddle offers six electronic "beeper" models and one model with neon indication for greater visibility when testing indoors. The beeper-style electronic detectors provide audible and visual indication of the presence of phase-to-ground ac voltages, in accordance with ANSI C84.1-1982 standards. The 6.9-KV model is equipped with a telescopic pole. All other models are fitted for universal spline mounting on a hot line pole rated for the voltage of the system being tested. Electronic voltage detectors for use on distribution line voltages (Cat. No.514360 series) provide a single red LED. Detectors rated for transmission line voltages (Cat. No. 514242 series) provide four LED's for improved visibility at greater distances. The neon-indicating voltage detector is designed for indoor testing of grounded ac systems. A bright neon indicator provides easy visibility in poor lighting conditions. During testing, the presence of voltages within the detector’s operating range will illuminate the bright neon lamp. A built-in piezoelectric voltage source provides a test feature to ensure that the detector is operative before use. The self-test is activated by a pushbutton. The neon detector is equipped with a 48-in. (1219-mm) telescopic pole calibrated and marked for voltages within the ratings of the detector. These demarcations assist the user in adjusting the pole to the length required for safe operation.
Phasing Testers (Five Models)
Tests both Grounded and/or ungrounded AC Systems
Models are Megger Numbers 510836-1, 514500-1, 514500-2, 514500-3 and 514500-4
DETEX Phasing Testers are available in five models for applications up to 69-kV class systems. The models include four analog phasing testers and one model with LED indication. The analog testers are ideally suited for outdoor testing of both grounded and ungrounded systems, especially in areas where an LED lamp is not easily visible. The large, 3.5-in.(89-mm) analog scale is calibrated to indicate the presence of nominal system voltages; the tester cannot be used to determine an exact voltage measurement.
Telescopic Pole for Safety
The 6.9-KV model is equipped with a telescopic pole. All other models are fitted for universal spline mounting on a hot line pole rated for the voltage of the system being tested.
Visually Alert Bright LEDs Indicates Presence of High Voltages
Electronic voltage detectors for use on distribution line voltages (Cat. No. 514360 series) provide a single red LED. Detectors rated for transmission line voltages (Cat. No. 514242 series) provide four LEDs for improved visibility at greater distances. The white LED-indicating voltage detector is designed for indoor testing of grounded ac systems. A row of bright LED indicators provide easy visibility in poor lighting conditions. During testing, the presence of voltages within the detector's operating range will illuminate the bright LED bulbs
Fail-Safe Prior Test Insures Proper Operation of DETEX Models
A built-in piezo-electric voltage source provides a self- test feature to ensure that the detector is operative before use. A pushbutton activates the self-test. Prior to testing, a self-test may be activated on the electronic detectors at the push of a button. The test simulates application of external voltage to the probe electrode, which verifies the operation of the buzzer and lights a red LED. When the TEST button is released, a green LED indicates the detector is operative and ready for use. If voltages within the detector's operating range are present during testing, the green LED extinguishes, the red LED Flashes and the audio tone sounds until the detector is removed from the voltage source.
Fail-Safe Tester for Voltage and Phase Detectors that Lack Self-Test
Megger Piezo Verifier 510006
This Biddle Megger Piezo verifier 510006 is an essential safety tool. This Biddle Megger tester is used to confirm the correct operation of voltage detectors and phasing testers that lack a self-testing capability. When the verifier handle is depressed at the rate of 3 strokes per second, the piezo crystal generates a safety check charge-voltage. This voltage, when applied to the tip of the detector tests for proper operation of the indicators. The Megger 510006 Piezo Verifier can be used with single and two pole models. It confirm the correct operation of voltage up to 30 KV, Generates 10KV, 20KV, and 30 KV is a small compact self powered Handheld tester.
Calibrated Telescopic Pole
The detector is equipped with a 48-in. (1219-mm) telescopic pole calibrated and marked for voltages within the ratings of the detector. These demarcations assist the user in adjusting the pole to the length required for safe operation. The pole retracts to 34 in. (864 mm) for convenient storage in a vinyl carrying case when not in use.
Megger DETEX Voltage Detectors |
Model |
Description |
514360-1 |
Operating Voltage Range: 2.3 to 7.2 KV; Mechanical Style: 51-In telescopic pole; Min Voltage: 1.2 KV; Nominal System Voltage Range: 2.4 to 6.9 KV |
514360-2 |
Operating Voltage Range: 4 to 14.5 KV; Mechanical Style: Spine fitted for attachment to a universal hot line pole; Min Voltage: 2.3 KV; Nominal System Voltage Range: 4.16KV to 13.8 KV |
514360-3 |
Operating Voltage Range: 11.7 to 36.2 KV; Mechanical Style: Spine fitted for attachment to a universal hot line pole; Min Voltage: 6.8 KV; Nominal System Voltage Range: 12KV to 34.5 KV |
514360-4 |
Operating Voltage Range: 24.3 to 72.5 KV; Mechanical Style: Spine fitted for attachment to a universal hot line pole; Min Voltage: 14 KV; Nominal System Voltage Range: 24.94KV to 69 KV |
514242-1 |
Operating Voltage Range: 67 to 235 KV; Mechanical Style: Spine fitted for attachment to a universal hot line pole; Min Voltage: 38 KV; Nominal System Voltage Range: 69KV to 230 KV |
514242-2 |
Operating Voltage Range: 200 to 550 KV; Mechanical Style: Spine fitted for attachment to a universal hot line pole; Min Voltage: 115 KV; Nominal System Voltage Range: 230KV to 500 KV |
| 514440-2 |
Operating Voltage Range: 3.6 to 36.5 KV; Mechanical Style: 48-in telescopic pole; Min Voltage: 2.1 KV; Nominal System Voltage Range: 4.16 to 34.5 KV |
DETEX Safe Continuous Monitoring of Phase-to-Ground Voltages
All DETEX models provide continuous monitoring of minimum phase-to-ground voltages as outlined by ANSI C84.1 standards, with conformance to lEC guidelines for capacitive high-voltage test instruments. Prior to testing, a self-test may be activated on the electronic detectors at the push of a button. The test simulates application of external voltage to the probe electrode, which verifies the operation of the buzzer and lights a red LED. When the TEST button is released, a green LED indicates the detector is operative and ready for use. If voltages within the detector's operating range are present during testing, the green LED extinguishes, the red LED Flashes and the audio tone sounds until the detector is removed from the voltage source.
Megger DETEX Phasing Testers |
510836-1 |
Nominal Voltage Range: 4.16 to 34.5 KV Neon; Kilo-Volt Indicator Markings: 0, 4.2, 7.2, 13, 25, 35; Mechanical Style: Two fixed-length poles with hand guards |
514500-1 |
Nominal Voltage Range: 2.4 to 6.9 KV; Kilo-Volt Indicator Markings: 0, 1.4, 2.4, 4.2, 6.9; Mechanical Style: Two fixed-length poles with hand guards |
514500-2 |
Nominal Voltage Range: 6.9 to 34.5 KV; Kilo-Volt Indicator Markings: 0, 4.2, 7.2, 13, 25, 35; Mechanical Style: Two fixed-length poles with hand guards |
514500-3 |
Nominal Voltage Range: 35.5 to 69 KV; Kilo-Volt Indicator Markings: 0, 13, 35, 69; Mechanical Style: Spline fitted for attachment to a universal hot line pole |
514500-4 |
Nominal Voltage Range: 6.9 to 34.5 KV; Kilo-Volt Indicator Markings: 0, 4.2, 7.2, 13, 25, 35; Mechanical Style: Spline fitted for attachment to a universal hot line pole |
ORDERING INFORMATION AT BOTTOM OF PAGE
Specifications at Bottom of Page
|